Trade Reference Path: Wire → Ampacity → Voltage Drop → Raceway

Voltage Drop Calculator

Branch & Feeder Voltage Drop Screener

Screen branch-circuit and feeder runs against target voltage drop limits before final field verification. Estimate voltage at the load, compare wire upsizing options, review NEC 250.122(B) EGC upsizing flags, and identify parallel-conductor or AC impedance conditions that need deeper review.

Run Inputs

Voltage Drop Calculator Inputs

Use single-phase 2-wire for 120 V, 208 V, 240 V, or 277 V loads that are not balanced 3-phase loads. Use balanced 3-phase only for actual 3-phase line-to-line equipment.
Enter the design load current for the conductor run being evaluated.
Enter one-way conductor length. Do not double the distance.
Applies a voltage-drop resistance multiplier only for screening. This is not an NEC Chapter 9 Table 8 temperature correction, ampacity adjustment, ambient correction, conductor-count derating, terminal temperature review, or raceway fill verification.
Use only when the run uses identical parallel conductors per phase and the installation is permitted for parallel conductors.

Parallel sets with conductors smaller than 1/0 AWG are not treated as a trusted voltage-drop result. Use 1 set, select 1/0 AWG or larger, or verify a code-permitted exception before relying on the output.

Use feeder-only when this run is only the feeder segment. Use total path only when the entered values represent the combined feeder and branch-circuit voltage-drop path.
This selection does not change the K-factor voltage-drop formula. It only downgrades result trust and flags when motors, drives, nonlinear loads, or power-factor-sensitive equipment need impedance, reactance, power factor, and manufacturer voltage-tolerance review.
Typical targets: 3% branch circuits, 5% total system. Adjust as needed for field conditions.

Compare calculated voltage drop against target limits and identify when conductor upsizing is required.

Ampacity Reminder

Voltage drop is a performance check only. The screening resistance adder changes the voltage-drop resistance estimate; it is not NEC Chapter 9 Table 8 temperature correction and does not verify conductor ampacity, ambient correction, conductor-count derating, terminal temperature limits, or raceway fill.

Advanced AC Review Required

This calculator uses resistance-based K-factor voltage-drop math as a field screening method. For large conductors, long feeders, 3-phase commercial runs, motor/compressor loads, VFDs, nonlinear loads, parallel large feeder sets, or power-factor-sensitive equipment, treat the displayed volts, percentage, and max-length values as resistance-only screening estimates. Do not treat a low calculated voltage drop as a final PASS. Verify AC impedance, reactance, power factor, raceway effects, and manufacturer voltage tolerance before final installation.

Input Review

Voltage
Basis
Load
Length
Material
Conductor
Parallel
VD Resistance Adj
Review
Load Type
Code Audit Date: May 2026 Source Scope: NEC 210, 215, 250.122(B) Result Scope: Voltage-drop screening and upsizing review Final Review: Ampacity, raceway fill, equipment, and AHJ verification required

Results Summary

Voltage Drop Output

Status

Compliance Boundary

This result checks voltage drop only. It does not approve conductor ampacity, OCPD sizing, ambient correction, conductor-count derating, terminal temperature limits, raceway fill, equipment nameplate requirements, local amendments, or AHJ acceptance.

Invalid Voltage-at-Load Condition

This result is forced to FAIL because the calculated voltage drop leaves the load voltage near zero, negative, or otherwise outside a usable screening range. Do not interpret this as a normal conductor-sizing result; review load current, one-way length, circuit voltage, conductor size, and design assumptions.

Parallel Conductor Block

This result is forced to FAIL because parallel sets were selected with a conductor smaller than 1/0 AWG. Do not use this output as a trusted installation path unless a code-permitted exception has been verified.

Recommended Action

3% is a recommended design target. Higher voltage drop may be acceptable depending on circuit type.

Reference:

What Changed

Voltage at Load

Advanced AC Review Required

K-factor voltage drop is a resistance-only screening estimate for these conditions. Do not use the displayed volts, percent drop, or max-length value as final voltage-drop approval for large conductors, long feeders, 3-phase commercial runs, motor/compressor loads, VFDs, nonlinear loads, parallel large feeder sets, or power-factor-sensitive equipment. Confirm AC impedance/reactance, power factor, raceway type, and manufacturer voltage tolerance before finalizing the run.

Recommended Conductor Size

Based on target voltage drop of %.

Parallel Recommendation Floor

Multiple parallel sets are selected, so the recommended conductor and upsizing ladder start at 1/0 AWG. Smaller conductors are not evaluated as recommendations for standard parallel power runs. Verify all parallel conductor installations against applicable NEC parallel conductor requirements and AHJ direction.

EGC Upsizing Review Required

If ungrounded conductors are larger than the minimum required for the OCPD due to voltage drop, verify equipment grounding conductor sizing. NEC 250.122(B) may require proportional EGC upsizing. This calculator does not know the breaker size or the baseline minimum conductor, so this advisory remains visible for usable results.

Next Raceway Check

This handoff sends the voltage-drop conductor size into the raceway fill check only. It does not mean the conductor is ampacity-compliant or approved for the circuit; verify ampacity, derating, terminal temperature limits, OCPD sizing, equipment grounding conductor sizing, and raceway fill before installation.

Check Raceway Fill Only

Upsizing Ladder

Parallel sets selected: ladder rows below 1/0 AWG are intentionally excluded for standard parallel power-run screening.

Reference Snapshot

System
Basis
Voltage
Current
Length
Material
Conductor
Parallel
VD Resistance Adder
Load Type
Field Reference

Voltage Drop Field Reference

Use this section to understand how the voltage drop result is produced, how the conductor upsizing ladder should be read, and which field checks still need to happen before conductor selection, raceway fill, equipment requirements, and AHJ review.

This calculator screens branch-circuit and feeder runs using the entered voltage, load current, circuit type, conductor material, selected wire size, one-way run length, and target voltage drop limit. The result estimates voltage at the load, percent drop, and whether the selected conductor stays within the chosen screening threshold.

When the selected conductor is above the target, the upsizing ladder compares larger conductor sizes so a field user can see how each step changes the voltage drop result. This helps avoid guessing whether the next size is enough or whether the job needs a larger jump before material is ordered or pulled.

The calculator also flags conditions that should not be treated as a simple resistance-only answer. NEC 250.122(B) EGC upsizing review, parallel conductor limits, motor or VFD loads, magnetic raceways, and large AC feeder conditions can all require additional field or engineering review.

The calculator uses a resistance-based field formula with circular-mil conductor area. It is intended for fast screening of common branch-circuit and feeder runs, not as a full AC impedance model for every installation.

Single-phase: VD = (2 × K × I × L) / CM

Three-phase: VD = (1.732 × K × I × L) / CM

In those formulas, K is the conductor resistance constant, I is load current in amps, L is one-way conductor length in feet, and CM is conductor circular-mil area. Enter one-way length only; the single-phase equation already accounts for the return path.

Large AC feeders, motor loads, VFDs, parallel feeders, and magnetic raceways may need NEC Chapter 9 Table 9 effective impedance review or engineering software before the result is used for final approval.

For a long 120V branch-circuit run, the calculation result can show why a conductor that is acceptable for ampacity may still deliver too little voltage at the load. In that case, the output is used to compare wire upsizing options, not to approve the entire circuit by itself.

For a detached garage or subpanel feeder, the same process helps compare voltage available at the load before the wire is pulled. A 60A, 240V feeder over a long one-way distance may need a larger conductor for performance even after the ampacity path has been checked.

The examples are screening workflows. Final conductor size still depends on ampacity, temperature correction, conductor-count adjustment, terminal rating, grounding, raceway fill, equipment instructions, and AHJ review.

The upsizing ladder shows larger conductor options and the estimated result for each size. This is useful when a foreman or estimator needs to decide whether the next conductor size is enough or whether the improvement is too small to justify the material change.

Treat the ladder as a voltage-performance comparison. It does not replace conductor ampacity review, small-conductor rules, terminal temperature limits, raceway fill, grounding, or equipment requirements.

If the selected conductor is increased because of voltage conditions, remember that the equipment grounding conductor may also require review. That is why the tool keeps the EGC reminder near usable results instead of hiding it below the page.

A common field miss happens when ungrounded conductors are increased to reduce voltage loss, but the equipment grounding conductor is left at the original size. NEC 250.122(B) can require proportional EGC upsizing when the ungrounded conductors are increased beyond the minimum size for reasons such as voltage performance.

This calculator does not know every project baseline: original OCPD, minimum ungrounded conductor, wiring method, equipment grounding path, and final raceway arrangement may not all be entered here. For that reason, the EGC warning is a review prompt rather than a final grounding-conductor size.

After using the ladder, confirm grounding and raceway conditions before installation. Larger conductors may change raceway fill, box fill, bend limits, pulling conditions, lug compatibility, and equipment termination requirements.

A favorable calculation result does not approve the conductor, circuit, or installation. It only means the entered run screened within the selected target using the assumptions shown in the result.

  • Conductor ampacity, ambient-temperature correction, conductor-count adjustment, and terminal-temperature limits.
  • OCPD selection, equipment grounding conductor sizing, bonding path, and fault-current conditions.
  • Raceway fill, box fill, pulling conditions, lug compatibility, equipment instructions, and AHJ acceptance.
  • Detailed AC impedance, harmonic, motor-starting, VFD, power-factor, or engineered study requirements.

Start with load and circuit basis. For dwelling service or panel-level checks, use the Residential Load Calculator or the Breaker Size Calculator before treating a run as ready for conductor selection.

Next, confirm conductor size and derating. Use the Wire Size Calculator for baseline conductor sizing, then verify ambient temperature, conductor count, and terminal-temperature basis with the Ampacity & Derating Calculator.

Use this page after the conductor path is known, especially for long branch-circuit or feeder runs. After any conductor upsizing, verify raceway fill with the Conduit Fill Calculator.

For EV charging circuits, screen continuous-load sizing first with the EV Charger Circuit Sizing Calculator, then use this calculation tool to check long-run performance. For source scope and code-basis notes, review the Voltage Drop Calculator code citation record.

Should I enter one-way length or round-trip length?

Enter one-way run length only. The formulas already account for the return path used by the calculation.

Why does the result show Screening Only instead of Pass?

Screening Only appears when the entered conditions are outside a simple final-answer path, such as large AC feeders, motor loads, VFDs, parallel conductors, magnetic raceways, or other conditions that may need deeper review.

Does this calculation result approve the conductor size?

No. The result only screens voltage at load and upsizing options. Ampacity, derating, terminal temperature, EGC sizing, raceway fill, equipment instructions, and AHJ requirements still need separate verification.

Why does the tool warn about EGC upsizing?

If ungrounded conductors are increased for voltage conditions, NEC 250.122(B) can require proportional equipment grounding conductor upsizing. The reminder is shown because the tool does not know every project baseline needed to approve the grounding conductor.

Why should I check ampacity and conduit fill after upsizing?

A larger conductor can change termination requirements, raceway fill, pull difficulty, box fill, and equipment compatibility. It also still needs ampacity and derating review before use in the field.

Why does the upsizing ladder show multiple conductor sizes?

The ladder compares larger conductors so you can see whether a small upsize is enough or whether the run needs a larger jump to meet the selected target limit.

TradeHub.tools provides field screening references for trained trade professionals. This page helps evaluate voltage at load and conductor upsizing options, but it does not replace project drawings, manufacturer instructions, engineered review, local amendments, inspection requirements, or AHJ decisions.

Before installation, confirm the complete circuit path: load basis, breaker or OCPD, conductor ampacity, derating, terminal temperature, grounding, raceway fill, equipment limitations, and site conditions.