NEC Code Audit Date
May 2026
Source scope: NEC Chapter 9 Table 1, Table 4, Table 5, Table 5A, and Table 8.
This calculator is built as a raceway fill reference for Chapter 9 area checks. It compares the total physical area of the entered conductors or cable assemblies against the allowable fill area for the selected raceway type and trade size.
- Table 1: Allowable raceway fill percentage. Table 1 supplies the fill limit used after the conductor count is known: 53% for one conductor, 31% for two conductors, 40% for three or more conductors, and 60% only for qualifying nipples 24 inches or less.
- Table 4: Raceway area by type and trade size. Table 4 provides the internal area used for EMT, PVC Schedule 40, PVC Schedule 80, IMC, and RMC selections. The calculator uses the selected raceway type and trade size rather than treating all conduit with the same nominal size as interchangeable.
- Table 5: Standard insulated conductor area. THHN, THWN, XHHW, and similar insulated conductor selections use the listed conductor area basis for the selected size and insulation family.
- Table 5A: Compact stranded aluminum area. Compact stranded aluminum is treated separately because its physical area can differ from standard stranded conductor entries. Use the compact option only when the conductor marking, submittal, or product data confirms compact stranding.
- Table 8: Bare grounding conductor area. Bare equipment grounding conductors still occupy raceway space. When bare grounding conductor mode is selected, this calculator uses the bare conductor area basis instead of an insulated conductor area.
What is outside this source scope?
This source scope does not approve conductor ampacity, voltage drop, conductor insulation suitability for the environment, box fill, pull tension, bending radius, raceway support, wet-location suitability, below-grade cover requirements, or local amendments. Use the fill result as the raceway space check, then continue the normal field review.