Skip to content
Trade Reference Workflow: Breaker → Wire → Voltage Drop
Wire Size Calculator · Trade Reference Workflow

Wire Size Calculator

Size conductors from load, material, terminal temperature, and field conditions before checking voltage drop.

Conductor Sizing Inputs

Enter the load and job conditions to size the conductor.

NEC 2026 • Code Audit April 2026

A. Load Entry

Start with the load value

Enter load. Tool converts to amps and applies continuous load rules if selected.

B. Conductor Settings

Set wire type and temperature limits

Terminal temperature limits final allowable ampacity. Derating is applied before this check.

C. Field Conditions

Conditions that affect wire size

Current-carrying conductors, ambient temperature, continuous load, and residential service rules affect the final wire size. These conditions reduce allowable ampacity and may require upsizing.

Count all current-carrying conductors in the raceway, not only this circuit. Neutrals may count for nonlinear loads.

Use the highest expected conductor temperature (attics, rooftops, mechanical rooms), not room temperature.

Continuous Load

Residential Main Service / Feeder

D. Results

Wire size decision

Enter load to enable calculation.

Field estimation tool. Verify against NEC tables, equipment ratings, and AHJ requirements.

Recommended Wire Size

Required Load

Why This Size

Governing Condition

Terminal Check

Derating Check

Tightest Margin

Field Insight

Adjustment Basis

Field Review Notes

Assumptions and checks

These notes keep the result tied to terminal limits, adjustment factors, conductor count, and real field conditions.

Voltage Drop Follow-Up

Check voltage drop before finalizing long runs

Use the selected conductor and load to verify voltage drop for long runs. The selected wire size, material, and load are carried into the voltage drop calculation.

Selected:
Material:
Load:
Open Voltage Drop Calculator

Decision Transparency

Why smaller wire sizes failed

This table shows the conductors tested before the final size was accepted. The selected row is the first conductor that passed terminal ampacity, adjusted ampacity, and small-conductor screening.

Derating Summary

Terminal Screen

Previous Size Review

Conductor Terminal Ampacity Adjusted Ampacity Small Conductor Limit Tightest Margin Decision

Action Row

Professional Use Notice

Field reference only — verify final installation conditions

This calculator is a field sizing reference based on NEC ampacity, terminal temperature, conductor adjustment, ambient correction, continuous-load screening, and dwelling service logic where selected. Final conductor selection must follow the adopted code cycle, equipment markings, engineered plans, local amendments, and Authority Having Jurisdiction (AHJ) interpretation.

Scope boundaries

  • Motor branch circuits and equipment sizing that require NEC Article 430 or manufacturer nameplate instructions.
  • Parallel conductor set design, conductor grouping, equal-length requirements, and high-ampacity commercial service layouts.
  • Medium-voltage installations, specialty equipment rules, local amendments, and engineered conductor specifications.
  • Equipment labels or manufacturer instructions that require a conductor larger than the calculator result.

Primary NEC References

NEC 110.14(C), 210.19(A), 215.2(A), 220.82, 240.4(D), 310.12, 310.15, 310.16, 334.80, and Article 430 are referenced for terminal limitations, branch/feeder conductor sizing, dwelling service allowance, derating, small-conductor screening, NM-B limits, and motor-load boundaries.

Review the full Code Citation & Source Log

Field Workflow Execution

How this calculator processes the job conditions

Load entry behavior

Amps, watts, and breaker entries are normalized into the required amp basis for conductor review. MCA is treated as an equipment nameplate input and bypasses the standard continuous-load toggle.

Terminal vs. derating checks

The selected conductor must pass the terminal temperature limit and the adjusted ampacity screen. The terminal column controls final ampacity; the adjustment column is used for conductor-count and ambient-temperature correction.

Decision table review

Each row shows why a conductor passes or fails. The selected conductor is the first size that clears terminal ampacity, adjusted ampacity after derating, and small-conductor screening where applicable.

After ampacity clears, check the run in the Voltage Drop Calculator and verify raceway space with the Conduit Fill Calculator .

Reference Tables

Verification Data Behind the Results

These values reflect the ampacity and adjustment factors used in the selection. Always verify against the adopted NEC edition and local AHJ requirements.

Copper Wire Ampacity Chart (NEC 310.16 reference)

Reference values used in the conductor sizing decision.

Size 60°C Cu 75°C Cu 90°C Cu
#14 AWG15A20A25A
#12 AWG20A25A30A
#10 AWG30A35A40A
#8 AWG40A50A55A
#6 AWG55A65A75A
#4 AWG70A85A95A
#2 AWG95A115A130A
1/0 AWG125A150A170A
2/0 AWG145A175A195A
4/0 AWG195A230A260A

Aluminum Wire Ampacity Chart (NEC 310.16 reference)

Reference values used in the conductor sizing decision.

Size 60°C Al 75°C Al 90°C Al
#12 AWG15A20A25A
#10 AWG25A30A35A
#8 AWG35A40A45A
#6 AWG40A50A55A
#4 AWG55A65A75A
#2 AWG75A90A100A
1/0 AWG100A120A135A
2/0 AWG115A135A150A
4/0 AWG150A180A205A

Ambient Temperature Correction Factors (NEC reference)

Used to adjust conductor ampacity based on jobsite temperature.

Ambient 75°C column 90°C column
30°C / 86°F1.001.00
35°C / 95°F0.940.96
40°C / 104°F0.880.91
45°C / 113°F0.820.87
50°C / 122°F0.750.82

Current-Carrying Conductor Adjustment Factors (NEC reference)

Used to reduce ampacity based on conductor count in the raceway or cable.

Current-carrying conductors Adjustment factor
1–3100%
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41+35%
Field Review

Common wire sizing questions and field mistakes

These answers walk through how sizing decisions hold up under real job conditions. Verify final values against the adopted NEC edition and local AHJ requirements.

Why does NM-B fail even though the insulation marking may show 90°C?
NM-B may be marked 90°C, but that doesn’t mean it can be used at that rating. At terminations, it’s limited to the 60°C column. The higher column can still be used for adjustment, just not for the final allowable ampacity. NEC reference: 334.80.
Why does derating use actual load amps instead of the 125% continuous-load value?
The 125% rule sets the conductor size at the terminal. Derating comes after that, based on heat conditions like conductor count and ambient temperature. If you apply 125% again during derating, you’re counting the same adjustment twice. NEC references: 210.19(A), 215.2(A), and 310.15.
Why did the tool select a larger wire even though the table value looked acceptable?
A conductor can look fine in the ampacity table and still fail once other checks come into play. Terminal limits, ambient temperature, conductor count, or small-conductor rules can all bring the allowable ampacity down. The decision table shows which condition controlled the final result. NEC references: 110.14(C), 240.4(D), 310.15, and 310.16.
When should the NEC 310.12 residential service toggle be used?
Use this only when the conductors serve the full dwelling load as a main service or qualifying feeder. It’s not meant for partial loads or equipment circuits. Even when applied, terminal limits and derating still control the final selection. NEC reference: 310.12.
Is voltage drop part of ampacity sizing?
No. Ampacity tells you how much current the conductor can safely carry. Voltage drop is different — it’s about performance over distance. You can pass ampacity and still need a larger wire for a long run.