SEER2
HSPF2
Field reference workflow | Manual J → Manual S → Manual D equipment selection
Screen HVAC equipment candidates against Manual J design loads using Manual S equipment screening checks. Review cooling capacity, sensible and latent fit, heating capacity, AHRI/OEM data status, and Manual D readiness before final equipment selection.
Confirm the Manual J design conditions. These values drive equipment selection and airflow requirements.
No Manual J data?
HVAC Load CalculatorCooling design load
Heating design load
Manual J Input Check
Manual S should start from completed Manual J design-load values, including total cooling, sensible cooling, latent load, heating load, and design conditions. Do not use rough tonnage guesses or incomplete field notes as equipment-selection inputs.
Filter the equipment list by brand, type, and nominal size before checking each candidate against the Manual J design point.
SEER2
HSPF2
The workflow screens the equipment list against total, sensible, latent, heating, and oversize limits, then prepares the selected blower/static reference values for Manual D.
Step 3 resolution
Calculated total
Calculated sensible
Calculated latent
Sizing deviation
Step 3 resolution
Candidate
Verification gate
Design point
Step 3 resolution
Closest candidate
Primary limiter
Design point
Manual J total
Manual J sensible
Manual J latent
Cooling cap
Interpolated total · sensible · latent
Performance data unavailable at this design point
Oversize
SEER2
EER2
HSPF2
Limiter
Status
Data incomplete
SEER2
EER2
HSPF2
Limiter
Data unavailable
AHRI Ref
SEER2
EER2
AHRI Airflow
Status
Data pending
Review the current screening outcome before printing, sharing, or carrying values forward.
Final-use output locked
Use the desktop right-side snapshot to review the current load, net capacity, deviation, and governing limiter while you work. Final selection details, print, and Manual D handoff stay gated until the professional acknowledgement is checked in Step 3.
Selected equipment
This selection clears all required capacity, manufacturer-data, AHRI, heating, and blower/static readiness checks for the current screening record.
Selection schedule
Calculated total
Calculated sensible
Calculated latent
Heating output
SEER2
HSPF2
Manual D bridge
Design CFM
Blower profile
TESP point
Delivered CFM
Coil ΔP
Filter ΔP
Next field step
TradeHub HVAC Workflow
Manual J defines the design load. Manual S screens the equipment at the actual design point. Manual D carries the selected airflow, blower, and pressure assumptions into the duct workflow. This page is the equipment selection step in that connected system.
Workflow position
Residential → Manual J → Manual S → Manual D
Dependency
Manual S should read a finished load profile first so total, sensible, latent, and winter design targets are grounded before equipment screening begins.
HVAC Load CalculatorCurrent page
This workflow compares manufacturer expanded performance data to the Manual J design point, then prepares the selected blower and pressure assumptions for the downstream airside workflow.
Next step
Once equipment clears the screen, use the selected airflow, TESP point, and device pressure drops as the starting reference for friction-rate and pressure-budget work.
Manual D Duct Design CalculatorTechnical Review
This workflow follows ACCA Manual S® equipment selection principles using Manual J® design loads and manufacturer expanded performance data. It supports structured screening of total, sensible, latent, and heating capacity against design conditions. Final equipment selection, AHRI matching, manufacturer data, and local code requirements should be verified prior to installation or permitting.
Manual S Field Reference
Use this reference after the calculator result to confirm the load inputs, identify jobsite conditions that can change the match, and carry only verified airflow and pressure assumptions into Manual D or equipment ordering.
The workflow starts with completed Manual J design-load values, then compares each equipment candidate using manufacturer expanded performance data instead of nominal tonnage alone. Cooling is screened at design outdoor dry bulb, entering wet bulb, and target airflow. Heating is screened at the selected winter design dry bulb and airflow target.
The workflow checks total capacity, sensible capacity, latent behavior, heating output, and oversize limits. It also carries the selected blower profile, delivered airflow point, and pressure-drop assumptions into the Manual D bridge so the airside design stays connected to the equipment choice.
Current selection status
Current candidate
Primary limiter
Confirm the Manual J load is final enough for equipment selection. Rough loads, changed windows, added rooms, duct leakage assumptions, or altered indoor design targets can move the Manual S result.
Verify that the selected match is supported by manufacturer expanded performance data at the entered outdoor dry bulb, entering wet bulb, airflow, and heating design conditions.
Check delivered airflow, blower profile, TESP assumptions, coil pressure drop, filter pressure drop, and accessory pressure drops before relying on the selection for Manual D.
Confirm the indoor unit, outdoor unit, refrigerant, efficiency rating, AHRI match, installation instructions, and local code requirements before ordering or permitting equipment.
Interpolated total cooling capacity is compared against the Manual J total load. Sensible capacity is checked against the sensible portion of the load, and latent behavior is reviewed as its own part of the split.
Heating output is screened at winter design temperature and target airflow so the selected system is not accepted on rated nameplate claims alone.
Passing a job is not only about being above the load. Candidates that exceed the selected cooling oversize band are flagged for review instead of being treated as automatic upgrades.
The selected result carries blower profile, delivered CFM, TESP point, and device pressure-drop assumptions so the equipment result can be checked again during Manual D duct design.
Start by verifying that the Manual J load inputs are complete enough for equipment selection.
Compare candidates using expanded performance data, not nominal tonnage alone.
Review delivered airflow, TESP, and pressure-drop assumptions before locking the equipment path.
Use the selected airflow and pressure assumptions as the starting point for duct friction-rate and pressure-budget work.
ACCA Source Alignment · April 2026
This workflow is aligned to ACCA Manual S® equipment selection principles and depends on Manual J® design loads, manufacturer expanded performance data, matched-system verification, and downstream Manual D® airflow coordination.
Use the result as a structured screening reference. Final equipment approval still requires current manufacturer data, AHRI match confirmation where applicable, installation instructions, local code review, and AHJ requirements.
It screens equipment candidates against Manual J design loads and identifies whether total capacity, sensible capacity, latent capacity, heating output, oversize limits, AHRI/OEM data status, and blower/static readiness are passing, failing, incomplete, or verification-required.
No. This is a screening and verification workflow. Final equipment selection must be confirmed against the exact OEM expanded performance data, AHRI match, blower data, installation instructions, jobsite conditions, and local requirements.
Nominal tonnage does not prove capacity at the actual design point. A candidate can still fail on total capacity, sensible capacity, latent balance, heating output, airflow assumptions, or oversize limits once Manual S-style checks are applied.
It means the capacity screen may look acceptable, but required field-use verification is not complete. The result should not be treated as a final Manual S match until AHRI/OEM data, manufacturer tables, and blower/static assumptions are confirmed.
Manual D handoff should only be used when the selected candidate has usable blower airflow, static pressure, and device pressure-drop assumptions. If that data is missing or verification-required, the handoff remains blocked.
The is currently under review for code alignment and field validation. Results are not yet available for use.
Status: In Review