Used as a quick field reference for identifying required residential branch circuits before load calculation and panel design.
01 Mandatory Home Branch Circuits (NEC 210.11(C))
| Circuit Type | Rating | Count | Code Reference |
|---|---|---|---|
| Small Appliance (Kitchen) | 20 Amp | Min. 2 | 210.11(C)(1) |
| Laundry Room | 20 Amp | Min. 1 | 210.11(C)(2) |
| Bathroom Receptacle | 20 Amp | Min. 1 | 210.11(C)(3) |
| Garage Receptacle | 20 Amp | Min. 1 | 210.11(C)(4) |
02 Technical Circuit Specifics & Requirements
Kitchen Small Appliance
These circuits must serve all wall and floor receptacle outlets, countertop outlets, and refrigeration equipment. No other outlets (like lighting) are permitted on these circuits.
Laundry Dedicated
This circuit is restricted to the laundry area only. It is intended for the washing machine and gas dryer ignition/controls. Electric dryers require a separate 30A circuit.
Garage & EV Readiness
NEC 210.11(C)(4) requires at least one 20A circuit for the garage. For 2026 compliance, verify local AHJ amendments for additional EVSE circuit requirements where applicable.
03 Standard Load Calculation Constants (VA)
Literal VA constants used for branch circuit sizing. These values are commonly carried forward into residential service and panel load calculations.
| Required Circuit | Load Value (VA) | NEC Citation |
|---|---|---|
| Kitchen (SABC) | 1,500 VA (each) | 220.52(A) |
| Laundry Room | 1,500 VA | 220.52(B) |
| Bathroom/Garage | Incl. in General VA | 220.14 |
Ready to size your service based on these circuits?
Run Load Calculation →Jurisdictional Precedence Notice
While this reference mirrors the 2026 National Electrical Code (NEC), users must verify local amendments with the Authority Having Jurisdiction (AHJ). Local requirements for AFCI protection and specific circuit counts vary significantly by municipal adoption.